Opti-Cell 150
OC-150 drift eliminators are designed to remove entrained water droplets from the leaving air stream at minimum pressure losses in both counter flow and cross flow cooling towers. Manufactured from rigid PVC sheets, they are fabricated from alternating corrugated and modified sine wave sheets bonded between 1.5” wide spacer sheets. The eliminators are resistant to ultraviolet light, rot, fungus, organic and inorganic solvents, acids, alkalis and chemicals typically found in cooling tower waters. Custom dimension modules and mil thicknesses are available upon request.
OC-150 / OC-80 DRIFT ELIMINATORS
PRODUCT | STANDARD GAUGES | RECOMMENDED SPAN1 | PRESSURE DROP @ .075 lb/ft3 | DRIFT RATE | ||
---|---|---|---|---|---|---|
(Mil Thickness) | 400 FPM | 500 FPM | 600 FPM | % Of Water Flow | ||
OC-150 | Cellular | |||||
15/15 | 4 | 0.019 | 0.029 | 0.040 | 0.002 | |
15/25 | 6 | 0.019 | 0.029 | 0.040 | 0.002 | |
OC-80 | Cellular | |||||
13/15 | 4 | 0.021 | 0.034 | 0.046 | 0.001 | |
20/30 | 8 | 0.021 | 0.034 | 0.046 | 0.001 |
1 Recommended Spans are based on a maximum air temperature of 1150F.
OC-150 FEATURES:
- Minimum Pressure Drop
- Multi-Pass High Efficient Drift Rate (.002%)
- Design For Use in Crossflow and Counterflow Applications
- Solvent Welded for Maximum Strength and Pack Integrity
- Material Complies with Cooling Technology Institute Standard 136
- Available in PVC or HPVC Material