Opti-Pac 7500 XF/ 7500IL / 7500ID
Available with an integrated louver and with an integrated drift eliminator, Opti-Pac 7500 film fill media are designed to replace OEM hanging fill sheets in crossflow cooling tower applications. The media are fabricated from rigid, thermoformed PVC sheets that are solvent-welded for maximum strength. They are resistant to UV, rot, fungus, organic/inorganic solvents, acids, alkalis, and chemicals normally found in cooling tower waters. The fill modules meet requirements of the Cooling Tower Institute’s standard for rigid PVC, STD-136.

PVC SHEET PROPERTIES:
Physical Property ASTM Test Units Value
Density D772 g/cm3 1.45
Tensile Strength (yield) D882 lb/in2 6,000 min
Flexural Strength D790 lb/in2 >11,000
Flexural Modulus D790 lb/in2 425,000 min
Elastic Modulus D638 lb/in2 360,000 min
IZOD Impact D256 ft-lb./in. 1.0 min
Impact Resistance D4226 in. lbs/mil 0.8 min
Heat Deflection D648 Deg F. 255 min
FlammabilityD635 Self extinguishing Less than 5 seconds
Flame Spread Rate E 84 Less than 20

 

Opti-Pac 7500 XF/ 7500IL / 7500ID FEATURES:
High Efficiency Design For Replacing Hanging Fill Sheets
Bottom Supported For Strength and Ease of Installation
Integrated Inlet Louver (IL) or Drift Eliminator (IDE)
Solvent Welded for Maximum Strength and Pack Integrity
Superior Water Distribution
Material Complies with Cooling Technology Institute Standard 136
Available in PVC or HPVC Material