5960 US Highway 64 East Ramseur, NC 27316     Phone: 336.824.2102     Fax: 336.824.2190     Email: mail@towercomponentsinc.com A wholly owned subsidiary of  Evapco
PRODUCTS - Drift eliminators
Opti-Cell 150
OC-150 drift eliminators are designed to remove entrained water droplets from the leaving air stream at minimum pressure losses in both counter flow and cross flow cooling towers. Manufactured from rigid PVC sheets, they are fabricated from alternating corrugated and modified sine wave sheets bonded between 1.5” wide spacer sheets. The eliminators are resistant to ultraviolet light, rot, fungus, organic and inorganic solvents, acids, alkalis and chemicals typically found in cooling tower waters. Custom dimension modules and mil thicknesses are available upon request.

OC-150 / OC-80 DRIFT ELIMINATORS

PRODUCT

STANDARD GAUGES

RECOMMENDED SPAN1

PRESSURE DROP
@ .075 lb/ft3

DRIFT
RATE

 

(Mil Thickness)

 

400
FPM

500
FPM

600
FPM

% Of
Water
Flow

OC-150

Cellular

15/15

4

0.019

0.029

0.040

0.002

15/25

6

0.019

0.029

0.040

0.002

OC-80

Cellular

13/15

4

0.021

0.034

0.046

0.001

20/30

8

0.021

0.034

0.046

0.001

1 Recommended Spans are based on a maximum air temperature of 1150F.

 

opti1200

OC-150 FEATURES:
Minimum Pressure Drop
Multi-Pass High Efficient Drift Rate (.002%)
Design For Use in Crossflow and Counterflow Applications
Solvent Welded for Maximum Strength and Pack Integrity
Material Complies with Cooling Technology Institute Standard 136
Available in PVC or HPVC Material
img

click here to download Installation Guide